Issue 4
947196
V-5580041A
ADA COMPLIANT STROBE
INTRODUCTION
These instructions contain the specifications and information
necessary to install, operate, and maintain the ADA Compliant
Strobe.
SPECIFICATIONS
Features
Cost effective and versatile solution to applications
requiring visual alerts or strobes
ADA compliant with a 99 Candella rating
Typical coverage of 4900 sq. ft. @ 80" mounting height
Supplied with accessories to fit almost any application
Activation Methods Dimensions/Weight
70 Volt amplified speaker signal 4.50"H x 4.50"W x 4.55"D
Dry contact closure (11.43cm H x 11.43cm W x 11.56cm D)
Electronic Message Sign 5V signal 1.38 lbs. (.63 kg)
Specifications
Brightness 99 Candella
Power supply operating voltage input 110VAC
Strobe minimum operating voltage 18VDC
Strobe maximum operating voltage 30VD
Current draw 196mA
Maximum instantaneous 450mA
Activation voltage requirements
Electronic message sign 40 A at 3 Volts
70 Volt audio signal 70 Volts peak
Activation voltage 70 Volts minimum 5 Volts
Environmental Rating Indoor
Connector Cable footage 6 feet
Mounting hardware 2 wall hangers
Lens color Amber
Faceplate cover Ivory
Metal case Silver